The cart is empty.
Dealers. First. Always.
DWG

EFLOW102NA8D Altronix Eight 8 PTC Outputs Power Supply/Charger with Multi-Output Access Power Controllers

SKU: EFLOW102NA8D
  • Eight (8) independently controlled output
  • Output options: Eight (8) Fail-Safe and/or Fail-Secure power outputs, Eight (8) form “C” 5A rated relay outputs, Any combination of the above
  • Eight (8) auxiliary power outputs (unswitched)
  • Output PTCs are rated @ 2.5A
  • Filtered and electronically regulated outputs
  • Supervision: AC Fail, Battery Fail and Battery Presence
  • Fire Alarm disconnect (latching or non-latching) is individually selectable for any or all of the eight (8) outputs
  • Alarm output relay indicates that FACP input is triggered
More details...
Ordering Notes: Dealers Only
MSRP Price: $666.00
Online Price: $476.00
Save to my Wish List

DWG Dealer Price : ---


Dealers - click here to set up your dealer account today.

Existing DWG Customers - Log In to view your current dealer pricing.



Previous Item   Next Item
Product Details

Altronix eFlowNAD series distribute and switch power to access control systems and accessories. They convert a 120VAC, 60Hz input into eight (8) independently controlled 12VDC or 24VDC Class 2 Rated power-limited PTC protected outputs. Outputs are activated by an open collector sink or normally open (NO) dry trigger input from an Access Control System, Card Reader, Keypad, Push Button, PIR, etc.


Specifications


Input

  • Voltage - 120VAC, 60Hz
  • Fusing - Varies, see Reference Chart.

Outputs

  • Class 2 Rated power-limited PTC Protected Outputs (auto-resettable).
  • Voltage - 12VDC or 24VDC, see Reference Chart.
  • Current - Varies, depending on the model.
  • Protection - PTC 2.0A.
  • Auxiliary - 3.5A (unswitched).
  • Other - Overvoltage protection. Filtered and regulated outputs.

Back-up Battery (not included)

  • Capacity
    • 12AH / 12VDC (1 or 2 within enclosure). 18AH / 40 AH / 65 AH (requires separate enclosure).
  • Type - Sealed lead acid or gel type.
  • Fuse Rating - Varies, see Reference Chart.
  • Failover - Upon AC loss, instantaneous.

Supervision

  • AC Failure - Form “C” contacts.
  • Battery - Form “C” contacts.
  • Low DC Power Shutdown - Shuts down DC output terminals if battery voltage drops below 71-73% for 12V units and 70-75% for 24V units (depending on the power supply). Prevents deep battery discharge.

Fire Alarm Disconnect

  • Supervised - Latching or non-latching, individually selectable for any or all of the eight (8) outputs.
  • EOL - 10K Resistor.

Indicators (LED)

  • Input - 120VAC is present.
  • DC Output - Powered
  • Relays - Individual LEDs indicate outputs are triggered (relays energized).
  • FACP - Indicates FACP disconnect is triggered.

Agency Listings

  • UL - UL294 - Access Control System Units
  • cUL - ULC-S319-05 - Electronic Access Control Systems. Class I Equipment; CSA C22.2 No.205 - Signal Equipment.
  • CSFM - California State Fire Marshall Approved.
  • CE - European Conformity.

Physical and Environmental

  • Dimensions (H x W x D) - 15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm).
  • Product Weight - 8.65 lbs. (3.92 kg)
  • Shipping Weight - 9.95 lbs. (4.51 kg)
  • Operating Temperature - 0ºC to 49ºC (32ºF to 120ºF)
  • Storage Temperature - -20ºC to 70ºC (-4ºF to 158ºF)
  • Relative Humidity - 85% +/-5%
  • BTU/Hr (12VDC/24VDC, approx.) - 61 BTU/Hr

EFLOW102NA8D Specifications PDF