MAXIMAL11V Altronix 16 Channel 3.5Amp 24VDC or 3.5Amp 12VDC Access Control Power Supply in UL Listed NEMA 1 Indoor 19” W x 26” H x 6.25” D Steel Electrical Enclosure

SKU: MAXIMAL11V
  • Sixteen (16) independently controlled outputs
  • Output options
    • a)Sixteen (16) Fail-Safe and/or Fail-Secure power outputs
    • b) Sixteen (16) form “C” 5A rated relay outputs
    • c) Any combination of the above
  • Sixteen (16) auxiliary power outputs (unswitched)
  • Output fuses are rated @ 3.5A
  • Filtered and electronically regulated outputs
  • Supervision: AC Fail, Battery Fail and Battery Presence
  • Fire Alarm disconnect (latching or non-latching) is individually selectable for any or all of the sixteen (16) outputs
  • Alarm output relay indicates that FACP input is triggered
More details...
Ordering Notes: Dealers Only
MSRP Price: $1,568.00
Web Price: $1,120.00
Save to my Wish List
Product Details

Maximal Access Power/Controllers distribute and switch power to access control systems and accessories. They convert a 220VAC (working range 198VAC - 256VAC), 50/60Hz input into sixteen (16) independently controlled 12VDC or 24VDC fuse protected outputs. These Fail-Safe/Fail-Secure power outputs may be converted to dry form “C” contacts. The outputs are activated by an open collector sink or normally open (NO) dry trigger input from an Access Control System, Keypad, Push Button, REX PIR, etc.


Specifications


Input

  • Voltage - 220VAC (working range 198VAC - 256VAC), 50/60Hz
  • Fusing - Varies, See Reference Chart

Output

  • Voltage - 12VDC or 24VDC, see Reference Chart
  • Current - Varies, see Reference Chart
  • Protection - Fused 3.5A
  • Auxiliary - 3.5A (unswitched)
  • Other - Overvoltage protection. Filtered and regulated outputs

Back-up Battery (not included)

  • Capacity - 12AH / 12VDC (up to 4 within enclosure), 40 AH / 65 AH (requires separate enclosure)
  • Type - Sealed lead acid or gel type
  • Fuse Rating - 15A @ 32VDC, Maximal33V does not have a battery fuse
  • Failover - Upon AC loss, instantaneous

Fire Alarm Disconnect

  • Supervised - Latching or non-latching, individually selectable for any or all of the sixteen (16) outputs
  • EOL - 10K Resistor

Supervision

  • AC Failure - Form “C” contacts
  • Battery - Form “C” contacts

Indicators (LED)

  • Input - 220VAC is present
  • DC Output - Powered
  • Battery - Discharged or not connected
  • Relays - Individual LEDs indicate outputs are triggered (relays energized)
  • FACP - Indicates FACP disconnect is triggered

Agency Listings

  • CE - European Conformity

Physical and Environmental

  • Dimensions (H x W x D) - 26” x 19” x 6.25” (660.4mm x 482.6mm x 158.75mm)
  • Product Weight - 43 lbs. (19.5 kg)
  • Shipping Weight - 47 lbs. (21.32 kg)
  • Operating Temperature - 0ēC to 49ēC (32ēF to 120ēF)
  • Storage Temperature - -20ēC to 70ēC (-4ēF to 158ēF)
  • Relative Humidity - 85% +/-5%
  • BTU/Hr. (approx.) - 12VDC: 43 BTU/Hr, 24VDC: 66 BTU/Hr, 12VDC and 24VDC: 55 BTU/Hr

MAXIMAL11V Specifications PDF