Dealers. First. Always.       |      The professional integrators favorite security distributor for over 20 years and counting.
DWG



Popular Everyday Products

MAXIMAL3FDV Altronix 16 Channel 6Amp 24VDC or 6Amp 12VDC Access Control Power Supply in UL Listed NEMA 1 Indoor 19 W x 26 H x 6.25 D Steel Electrical Enclosure

SKU: MAXIMAL3FDV
  • Altronix eFlow6NB UL Listed Sub-Assembly power supply/charger converts a 120VAC, 60Hz input into a single 12VDC or 24VDC output.
  • It also offers a suite of features that includes fire alarm disconnect, overvoltage protection, and low power disconnect which prevents deep discharge of stand-by batteries
More details...
Ordering Notes: Dealers Only
MSRP Price: $1,308.00
Online Price: $934.00


DWG Dealer Price : ---


Dealers - click here to set up your dealer account today.

Existing DWG Customers - Log In to view your current dealer pricing.



MAXIMAL3FDV Altronix 16 Channel 6Amp 24VDC or 6Amp 12VDC Access Control Power Supply in UL Listed NEMA 1 Indoor 19 W x 26 H x 6.25 D Steel Electrical Enclosure
MAXIMAL3FDV Altronix 16 Channel 6Amp 24VDC or 6Amp 12VDC Access Control Power Supply in UL Listed NEMA 1 Indoor 19 W x 26 H x 6.25 D Steel Electrical Enclosure
Previous Item   Next Item
 
Product Details

EFLOW6NB Specifications


Input

  • Voltage - 120VAC, 60Hz, 3.5A max
  • Fuse Rating - 5A / 250V

Outputs

  • Voltage - 12VDC or 24VDC selectable
  • Current - 6A continuous max.
  • Auxiliary - Power-limited @ 1A (unswitched).
  • Other- Overvoltage protection. Filtered and regulated.

Back-up Battery (not included)

  • Type - Sealed lead acid or gel type.
  • Fuse Rating - 10A @ 32VDC.
  • Failover - Upon AC loss, instantaneous.

Fire Alarm Disconnect

  • Supervised - Latching or non-latching.
  • EOL - 10K Resistor.

Supervision

  • AC Failure - Form "C" contacts.
  • Battery - Form C" contacts.
  • Low DC Power Shutdown - Shuts down DC output terminals if battery voltage drops below 71-73% for 12V units and 70-75% for 24V units (depending on the power supply). Prevents deep battery discharge.

Indicators (LED)

  • Input - 120VAC is present.
  • DC Output - Powered.

Agency Listings

  • UL - Access Control - UL294, Burglar Alarm - UL603, Fire Alarm - UL1481
  • cUL - Burglar Alarm - ULC-S318-96, Access Control - ULC-S319-05, Signal Equipment - CSA C22.2 No.205

Physical and Environmental

  • Dimensions (H x W x D) - 7.5 x 4.6 x 1.75 (190.5 mm x 116.8 mm x 44.5 mm).
  • Product Weight - 0.8 lbs. (0.36 kg).
  • Shipping Weight - 0.95 lbs. (0.43kg).
  • Operating Temperature - 0C to 49C (32F to 120F).
  • Storage Temperature - -20C to 70C (-4F to 158F).
  • Relative Humidity - 85% +/-5%
  • BTU/Hr (approx.) 12VDC - 37, 24VDC - 74

ACM8CB Specifications


Input

  • Voltage
    • 12 to 24 VAC or VDC operation (setting not required), 0.6A @ 12V, 0.3A @ 24V current consumption with all relays energized
    • Main fuse is rated at 10A
  • Trigger Inputs - Eight (8) Access Control System trigger inputs:
    • Eight (8) normally open (NO) inputs
    • Eight (8) open collector sink inputs
    • Any combination of the above
  • Input Options
    • One (1) common power input (board and lock power)
    • Two (2) isolated power inputs (one (1) for board power and one (1) for lock/accessory power)

Outputs

  • Eight (8) independently controlled Class 2 Rated
  • PTC protected power-limited auto-resettable 2.5A outputs:
    • Eight (8) Fail-Safe and/or Fail-Secure power outputs
  • Eight (8) auxiliary power outputs (unswitched)
  • Output ratings - Output PTCs are rated 2.5A each
  • Note - Total output current is determined by the power supply, not to exceed a maximum of 10A total

Indicators (LED)

  • Red LEDs - Outputs are triggered (relays energized)
  • Green LED - FACP disconnect is triggered

Agency Listings

  • UL
    • UL294 - Access Control System Units
  • cUL
    • CSA Standard C22.2 No.205-M1983 - General Signaling Equipment

Physical and Environmental

  • Dimensions (L x W x H) - 8" x 4" x 0.75" (203.2mm x 114.3mm x 19.1mm)
  • Product Weight - 0.65 lbs. (0.29 kg)
  • Shipping Weight - 0.85 lbs. (0.39 kg)
  • Temperature
    • Operating - 0C to 49C (32F to 120F)
    • Storage - -20C to 70 C (-4F to 158F)
  • Relative Humidity - 85% +/-5%
  • BTU/Hr (approx.) - 4 BTU/Hr

EFLOW6NB Specifications PDF

EFLOW6NB Installation Manual

ACM8CB Specifications PDF

ACM8CB Installation Manual


Product Reviews