  • Universal full event sole & dual path 5G LTE-M cellular &/or IP commercial fire alarm reporting from any panel brand, virtually anywhere nationwide.
  • Code-compliant, replaces 2 POTs lines per FACP & saves thousands of dollars per year over the leased landlines.
  • Supports 12V-24V control panels and FACPs that communicate using Contact ID and 4/2 (such as on legacy panels).
  • Proven StarLink Reliability & Best 5G LTE-M Performance – Works where others can’t - Signal Boost™ Circuitry & unique dual-diversity twin antennas, maximizing signal acquisition and eliminating the multiphase-effect signal-clash/ drop-outs single-antenna units are prone to.
  • Full Data Reporting to any Central Station nationwide, via choice of Verizon® or AT&T® Networks. Communicate critical life and safety alarm reports for maximum life safety & liability protection.
  • Easiest installation, powered by panel, NO extra power supply, NO extra conduit. (Excludes Metal Enclosure Direct AC-Powered models)
More details...
MSRP Price: $298.58
Save to my Wish List

DWG Dealer Price : ---


Dealers - click here to set up your dealer account today.

Existing DWG Customers - Log In to view your current dealer pricing.



Previous Item   Next Item
Product Details

The SLE-MAXVI-FIRE and SLE-MAXAI-FIRE Sole/Dual-Path Alarm Communicators are specifically designed to interface with FACP (Fire Alarm Control Panels) and to comply with UL 864. The SLE-MAXVI-FIRE operates on the Verizon network, the SLE-MAXAI-FIRE on the AT&T network and both models utilize CAT-M1 technology. These devices support both Sole Path and Dual Path communication. Sole Path communication is cellular only and Dual Path communication is cellular and IP, which requires connection to the local network using the on-board Ethernet jack or via Wi-Fi using the optional UL 864 Certified SLE-WIFI-MODULE.


Specifications


Electrical Ratings for +12V / 24V (powered by the control panel)†

  • Input Voltage - 10-24VDC regulated (power-limited output from Certified control panel Aux/Remote Fire Power)
  • Input Current - 10VDC standby: 115mA, 12VDC standby: 101mA, 15VDC standby: 92mA, 24VDC standby: 85mA
  • Wi-Fi Module - (Optional) Add 45mA to the above. (With peak RF transmission current of 325mA)

Electrical Ratings for the IN 1 Fire Input

  • Input Voltage - 9-25VDC
  • Maximum Input Current - Up to 2mA from FACP NAC circuit

Electrical Ratings for IN 2, IN 3, IN 4, and IN 5: (Inputs IN 2, IN 3, IN 4, and IN 5 are Class B)

  • Maximum Loop Voltage - 25VDC input
  • Maximum Loop Current - 1.7mA
  • End of Line Resistor (EOLR) Value - 10K

Electrical Ratings for PGM3 Output

  • Open Collector Output - Maximum Voltage 25VDC
  • Maximum PGM Sink Current - 50mA (up to 15VDC), 25mA (15.1VDC - 25VDC)

Physical (W x H x D)

  • Plastic Housing - 8 x 5-29/64 x 1˝" (20.3 x 13.9 x 3.8cm)
  • Mounting - Plastic housing includes three keyhole slots for triple gang boxes
  • Antenna Length - 8.25" (21cm)

Environmental

  • Operating Temperature - 0°C - 49°C (32°F - 120°F)
  • Humidity - Maximum 93% Non-Condensing
  • Environment - Indoor / dry location use only