The cart is empty.
Dealers. First. Always.
DWG

SLE-MAXVI-CFB Napco StarLink Max Fire Dual Path Commercial Fire/Burglar 5G LTE-M Cellular and WiFi Alarm Communicator - Red Metal Enclosure - Powered by Control Panel - Verizon Network

SKU: SLE-MAXVI-CFB
  • Power limited output to the StarLink communicator PC board 12V input terminals
  • Battery connection red and black flying leads
  • Monitored battery charging and Active battery test circuits
  • StarLink communicator trouble input (from StarLink PC-board PGM1 terminal to detect StarLink communicator trouble)
  • Requires a sealed lead acid min 4AH / max 7AH battery for minimum 24-hour standby time (max charge current 200mA)
  • Trouble relay output (C, N/O and N/C terminals) to wire to a panel zone dedicated to "Communicator Trouble" (dry contacts). Remove jumper "J2" isolate relay OUT1 common from ground
  • Green AC ON LED visible from the exterior housing
  • Yellow TROUBLE LED "D4" on PC board. Flashes signify:
    • One flash: AC fail / brownout
    • Two flashes: Low battery
    • Three flashes: Charging circuit trouble
    • Four flashes: StarLink communicator trouble
More details...
MSRP Price: $373.24
Save to my Wish List

DWG Dealer Price : ---


Dealers - click here to set up your dealer account today.

Existing DWG Customers - Log In to view your current dealer pricing.



Previous Item   Next Item
Product Details

The StarLink MAX Series Sole/Dual-Path Commercial / Residential Fire alarm capture IP communicators are fully supervised, wireless digital two-way subscriber units. The SLE-MAXVI-CFB and SLE-MAXVI-CFBPS communicators operate on the Verizon network, the SLE-MAXAI-CFB and SLE-MAXAI-CFBPS on the AT&T network and all models utilize CAT-M1 technology. These devices support both Sole Path and Dual Path communication. Sole Path communication is cellular only and Dual Path communication is cellular and IP, which requires connection to the local network using the on-board Ethernet jack or via Wi-Fi using the optional UL 864 Certified SLE-WIFI-MODULE.


Specifications


Electrical Ratings for 120VAC, 60Hz For Models with Power Supply (SLE-MAXVI-CFBPS and SLE-MAXAI-CFBPS)

  • Input Voltage - 120VAC nominal
  • Input Current - 200mA maximum
  • Maximum Charging Current - 200mA

Electrical Ratings for +12V / 24V For Models without Power Supply (SLE-MAXVI-CFB and SLE-MAXAI-CFB)†

  • Input Voltage - 10-24VDC regulated (power-limited output from UL Certified control panel Aux/Remote Fire Power)
  • Input Current - 10VDC standby: 115mA, 12VDC standby: 101mA, 15VDC standby: 92mA, 24VDC standby: 85mA
  • Wi-Fi Module - (Optional) Add 45mA to the above, (With peak RF transmission current of 325mA)

Electrical Ratings for the IN 1 Fire Input

  • Input Voltage - 9-25VDC
  • Maximum Input Current - Up to 2mA from FACP NAC circuit

Electrical Ratings for IN 2, IN 3, IN 4, and IN 5: (Inputs IN 2, IN 3, IN 4, and IN 5 are Class B)

  • Maximum Loop Voltage - 25VDC
  • Maximum Loop Current - 1.2mA
  • End of Line Resistor (EOLR) Value - 10K (2 req'd)

Electrical Ratings for PGM3 Output

  • Open Collector Output - Maximum Voltage 3V when active; 25V maximum when not active
  • Maximum PGM Sink Current - 50mA (up to 15VDC), 25mA (15.1VDC - 25VDC)

Physical (W x H x D)

  • Metal Housing - 11½ x 9½ x 3½" (29.2 x 24.1 x 8.9cm)
  • Mounting - Metal housing includes two keyhole slots for wall mounting
  • Antenna Length - 8.25" (21cm)

Environmental

  • Operating Temperature - 0°C - 49°C (32°F - 120°F)
  • Humidity - Maximum 93% Non-Condensing
  • Environment - Indoor / dry location use only

SLE-MAXVI-CFB Specification Pdf


Product Reviews

Write your own review

 

Rate this product:


DWG - 800 Shames Drive , Westbury , NY 11590 , USA - 516-933-4900
Connect with us on Social Media   Facebook   Instagram   Twitter   Linked In