MAXIMAL33 Altronix 16 Output Fused Power Supply/Charger w/ Controller and Enclosure 12VDC @ 5.5Amp or 24VDC @ 5.7Amp

SKU: MAXIMAL33
  • Sixteen (16) independently controlled outputs.
  • Output options - Sixteen (16) Fail-Safe and/or Fail-Secure power outputs, Sixteen (16) form “C” 5A rated relay outputs, Any combination of the above.
  • Sixteen (16) auxiliary power outputs (unswitched).
  • Output fuses are rated @ 3.5A.
  • Filtered and electronically regulated outputs.
  • Supervision - AC Fail, Battery Fail and Battery Presence.
  • Fire Alarm disconnect (latching or non-latching) is individually selectable for any or all of the sixteen (16) outputs.
  • Alarm output relay indicates that FACP input is triggered.
  • Fire Alarm disconnect input options - Normally open (NO) or normally closed (NC) dry contact input, Polarity reversal input from FACP signaling circuit.
  • Built-in charger for sealed lead acid or gel type batteries.
  • Instantaneous transfer to stand-by batteries.
  • UL Listed in the U.S. and Canada.
  • Lifetime Warranty / Made in the U.S.A.
More details...
Ordering Notes: Dealers Only
MSRP Price: $1,616.00
Web Price: $1,154.00
Save to my Wish List
Product Details

Maximal33 distributes and switches power to access control systems and accessories. It converts a 115VAC 60Hz input into sixteen (16) independently controlled 12VDC or 24VDC fuse protected outputs. These Fail-Safe/Fail-Secure power outputs may be converted to dry form "C" contacts. The outputs are activated by an open collector sink or normally open (NO) dry trigger input from an Access Control System, Keypad, Push Button, REX PIR, etc.


Specifications


Input

  • Voltage - 115VAC, 60Hz.
  • Fusing - Varies, See Reference Chart.

Outputs

  • Voltage - 12VDC and/or 24VDC, see Reference Chart.
  • Current - Varies, see Reference Chart.
  • Protection - Fused 3.5A.
  • Auxiliary - 3.5A (unswitched).
  • Other - Overvoltage protection, Filtered and regulated outputs.

Back-up Battery(not included)

  • Capacity - 12AH / 12VDC (up to 4 within enclosure). 40 AH / 65 AH (requires separate enclosure).
  • Type - Sealed lead acid or gel type
  • Fuse Rating - 15A @ 32VDC Maximal33 does not have a battery fuse.
  • Failover - Upon AC loss, instantaneous.

Fire Alarm Disconnect

  • Supervised - Latching or non-latching, individually selectable for any or all of the sixteen (16) outputs.

Supervision

  • AC Failure - Form "C" contacts.
  • Battery - Form "C" contacts.

Indicators (LED)

  • Input - 115VAC is present.
  • DC Output - Powered.
  • Battery - Discharged or not connected.
  • Relays - Individual LEDs indicate outputs are triggered (relays energized).
  • FACP - Indicates FACP disconnect is triggered.

Agency Listings

  • UL - UL294 Access Control System Units.
  • cUL - C22.2 No.205-M1983 General Signaling Equipment
  • CSFM - California State Fire Marshall Approved.

Physical and Environmental

  • Dimensions (H x W x D) - 26" x 19" x 6.25" (660.4mm x 482.6mm x 158.75mm).
  • Product Weight - 31.6 lb. (14.3 kg)
  • Shipping Weight - 38.6 lb. (17.5 kg)
  • Operating Temperature - 0°C to 49°C (32°F to 120°F).
  • Storage Temperature - -20°C to 70°C (-4°F to 158°F).
  • Relative Humidity - 85% +/-5%.
  • BTU/Hr. (approx.) - 12VDC - 68, 24VDC - 140, 12VDC and 24VDC - 104

MAXIMAL33 Specifications PDF