The cart is empty.
Dealers. First. Always.
DWG

MAXFIT38AP Altronix AL600ULXB, ACM8/PD8UL-BC750

SKU: MAXFIT38AP
  • Altronix AL600ULXB UL Listed Sub-Assembly power supply/charger converts a 115VAC, 60Hz input into a single 12VDC or 24VDC non-power-limited output
  • It also offers a suite of features that includes AC fail supervision, battery presence, and low battery supervision
More details...
Ordering Notes: Dealers Only
MSRP Price: $1,018.00
Web Price: $727.00
Save to my Wish List
Product Details

AL600ULXB Specifications


Inputs

  • Voltage - 115VAC, 60Hz, 3.5A max
  • Fusing - 5A / 250V.

Outputs

  • Voltage - 12VDC or 24VDC selectable.
  • Current - 6A continuos supply current.
  • Other - Short circuit and thermal overload protection. Filtered and regulated.

Back-up Battery (not included)

  • Type - Sealed lead acid or gel type.
  • Failover - Upon AC loss, instantaneous.

Supervision

  • AC Failure - Form "C" contacts.
  • Battery - Form "C" contacts.

Indicators (LED)

  • Input - 115VAC is present.
  • DC Output - Powered.
  • Battery - Discharged or not connected.

Agency Listings

  • UL
    • Access Control - UL294
    • Burglar Alarm - UL603
    • Fire Alarm - UL1481
  • cUL
    • Signal Equipment - CSA C22.2 No.205-M1983

Physical and Environmental

  • Dimensions (L x W x H) - 7.1" x 4.5" x 2" (180.3 mm x 114.3 mm x 50.8 mm).
  • Product Weight - 0.8 lbs. (0.36 kg).
  • Shipping Weight - 0.95 lbs. (0.43 kg).
  • Temperature
    • Operating - 0°C to 49°C (32°F to 120°F).
    • Storage - -20°C to 70°C (-4°F to 158°F).
  • Relative Humidity - 85% +/-5%
  • BTU/Hr. (approx.)
    • 12VDC - 37 BTU/Hr.
    • 24VDC - 74 BTU/Hr.

ACM8 Specifications


Input

  • Voltage
    • 12 to 24 VAC or VDC operation (setting not required), 0.6A @ 12V, 0.3A @ 24V current consumption with all relays energized
    • Main fuse is rated at 10A
  • Trigger Inputs - Eight (8) Access Control System trigger inputs:
    • Eight (8) normally open (NO) inputs
    • Eight (8) open collector sink inputs
    • Any combination of the above
  • Input Options
    • One (1) common power input (board and lock power)
    • Two (2) isolated power inputs (one (1) for board power and one (1) for lock/accessory power)

Outputs

  • Eight (8) independently controlled 2.5A outputs:
    • Eight (8) Fail-Safe and/or Fail-Secure power outputs
    • Eight (8) dry form “C" 5A rated relay outputs
    • Any combination of the above
  • Eight (8) auxiliary power outputs (unswitched)
  • Output ratings - Output fuses are rated 3.5A each
  • Note - Total output current is determined by the power supply, not to exceed a maximum of 10A total

Indicators (LED)

  • Red LEDs - Outputs are triggered (relays energized)
  • Green LED - FACP disconnect is triggered

Agency Listings

  • UL
    • Access Control - UL294
  • cUL
    • General Signaling Equipment Evaluated to CSA Standard C22.2 No.205-M1983

Physical and Environmental

  • Enclosure Dimensions (H x W x D) - 8" x 4" x 0.75" (203.2mm x 114.3mm x 19.1mm)
  • Product Weight - 0.65 lbs. (0.29 kg)
  • Shipping Weight - 0.85 lbs. (0.39 kg)
  • Temperature
    • Operating - 0°C to 49°C (32°F to 120°F)
    • Storage - -20°C to 70° C (-4°F to 158°F)
  • Relative Humidity - 85% +/-5%
  • BTU/Hr (approx.) - 4 BTU/Hr

PD8UL Specifications


Input

  • Voltage Range - 12VDC or 24VDC, up to 10A or 24VAC or 28VAC, up to 12A.

Outputs

  • Eight (8) fuse protected outputs.
  • 2.5A per output max.
  • Total output current should not exceed max current rating of power supply employed.
  • Fuses are rated @ 3.5A/250V.

Indicators (LED)

  • DC Output - Power LED.

Agency Listings

  • UL - UL294 Access Control, UL603 Burglar Alarm, UL1481 Fire Alarm
  • cUL - General Signaling Equipment Evaluated to CSA Standard C22.2 No.205-M1983., Power Supplies for Burglar Alarm Systems ULC-5318-96.

Physical and Environmental

  • Dimensions (H x W x D) - 5.25" x 3.25" x 1" (133.4mm x 82.6mm x 25.4mm).
  • Product Weight - 0.15 lbs. (0.07 kg).
  • Shipping Weight - 0.25 lbs. (0.11 kg).
  • Operating Temperature - 0°C to 49° (32°F to 120°F).
  • Storage Temperature - -20°C to 70°C (-4°F to 158°F).
  • Relative Humidity - 85% +/-5%.

BC750 Specifications


Features

  • 19 Gauge steel enclosure
  • Ample knockouts accommodating either 3/4” or 1” conduits for convenient access
  • Cam lock and keys are included

Capacity

  • Fits up to four (4) 12VDC/12AH batteries

Physical and Environmental

  • Dimensions (H x W x D) - 20.5” x 16.5” x 6.25” (520.7mm x 419.1mm x 158.8mm)
  • Product Weight - 19.4 lb. (8.8 kg)
  • Shipping Weight - 24.8 lb. (11.25 kg)

AL600ULXB Specifications Sheet

ACM8 Specifications Sheet

PD8UL Specifications Sheet

BC750 Specifications Sheet


Product Reviews