The cart is empty.
Dealers. First. Always.
DWG

FPO250-3D8PE12M LifeSafety Power Mercury 24 Door 20 Amp 12VDC 24 Auxiliary Class II Distribution Outputs Access Control Power Supply in UL Listed Indoor 36" W x 48" H x 8" D Electrical Enclosure

SKU: FPO250-3D8PE12M
  • 120 or 230 VAC input
  • 12 and 24 VDC outputs
  • On board Fire Alarm Interface
  • Continuous and resettable DC
  • 24 auxiliary, class 2 power ltd at 2.5A each
  • Increased power, multiple voltages
  • Additional distribution outputs
  • Network monitoring and reporting
More details...
Availability: 2 to 3 Week Lead Time
MSRP Price: $5,139.00
Web Price: $3,427.00
Save to my Wish List
Product Details

MCLASS Unified Power Systems combine FlexPower power modules alongside Mercury Security access hardware in one compact and secure UL Listed solution.

The FPO Power Supply / Battery Charger provides two power outputs user selectable for 12 or 24 VDC. One output provides continuous output power for system use, the second is resettable output power, activated when the fire alarm disconnect is initiated.


Specifications


Input Power

  • Input 120/230 VAC 50/60 Hz | 282 Watts (2.35A)
  • Overload and short circuit protection
  • Over temperature protection
  • Polarized AC power supply disconnect

Output Power

  • FPO250: 12V/20A or 24V/10A | 250 Watts
  • Outputs: Continuous (DC1) Resettable (DC2)
  • 24 auxiliary outputs, Class II power limited at 2.5A each
  • 120 mV output voltage ripple
  • System Efficiency: 87% | System BTU Rating: 66 BTU/Hr

Battery Charging

  • Independent built-in 2A charger for sealed lead-acid or gel type batteries
  • Microprocessor dual rate charging of 12 or 24V battery sets
  • Automatic switchover to standby battery when AC fails
  • Zero voltage drop when switched over to battery backup

Supervision

  • AC Fault (form "C" contacts)
  • System Fault (form "C" contacts) may be triggered by low/no battery, short to earth ground and power supply failure

Visual Indicators

  • AC input, DC1 and DC2 output
  • System fault
  • AC fault
  • Short to earth ground
  • Reverse battery polarity
  • Fire Alarm Input activated
  • D8P: DC outputs

Regulatory Compliance Mercury/LSP Joint Listing

  • UL294, UL603, UL1076, ULC S318, ULC S319 CSA C22.2 #107.1, CSA 22.2 #60950
  • FCC Part 15, Subpart B, CE

Enclosure Dimensions

  • Size: 48.00H x 36.00W x 8.00D in. (122.00 x 91.00 x 20.30 cm) | Weight: 120 lbs

Access Panel Mounting

  • LP1502, LP4502, LP2500, MR50, MR52, MR16, LNL-500, 1100, 1200, 1320, 2000, 2220, 3300

FPO250-3D8PE12M Specifications PDF